Measures for the employee against exposure to contaminated SF6 in event of emergency
Before you begin
- Use the following personal protective equipment:
- Disposable overall
- Rubber or neoprene gloves
- Rubber or neoprene boots
- Full face mask with B2 P3 filter or a fresh air cap.
- Before you enter the space measure the SF6 concentration. If it is higher than 60 mg/m3 (10 ppm), you may not enter the space.
- Ventilate the space before you enter. If mechanical ventilation is available, switch it on.
- Evacuate the location and set up safety zones.
During the work
- Continuously measure the SF6 concentration, it must be lower than 60 mg/m3 (10 ppm). Otherwise leave the space.
- Remove loose dust with a vacuum cleaner with a high efficiency particulate air filter on the exhaust side.
- Remove any dust which adheres with a non-fraying dry material.
After cleaning you can continue working in the compartment without the above personal protective equipment.
When the work is finished
- Clean the tools and personal protective equipment with the vacuum cleaner or with a non-fraying dry cloth or a 10% soda solution.
- Clean the vacuum cleaner compartment with a cloth drenched in 10% soda solution and place the filter and the vacuum cleaner dust bag in a 10% soda solution for 24 hours.
- Dispose of the waste as hazardous waste.
- After ending or interrupting the work activities wash hands and face with soap and water.
Oplossing voor:
Werknemer
Oplossing status:
Goedgekeurd door de Nederlandse Arbeidsinspectie